Infrared Thermal Imaging Inspection

  • Tags: Infrared Thermal Imaging Inspection , 积分 Counts:36 次

NAME

Capacitor Compensation Cabinet

EQUIPMENTS INPORMATION

Location

East distribution room

Name Plate

42142

Load

Rated Load

Object Type

Fuse

Used Year

Unknown

Maintain

Unknown

 

IR IMAGE

CONSULT IMAGE

 

EXAMINATION ENVIRONMENT

Weather

Indoor

Temp

29

Distance

1m

Humidity

57%

 

IMAGE INFORMATION

Object

Max

ΔT

Current(A)

Sp1 /Sp2 /Sp3 /Sp4

97.7/88.4/83.7/71.9

68.7/59.4/54.7/42.9

40

PROBLEM DESCRIPTION

 1.The temperature of Sp1 is 9.4 higher than Sp2, Judged from the field test, The installation of fuses are bad.2.The temperature of Sp4,.Sp2, Sp3 is inconsistent, So Fuse is not the same degree of aging.

RECOMMEND ACTION

Repair Priority

High

Advise: When necessary, replace the fuse, And to ensure that the installation of fuses in place